Students training aid for how to carryout the safe isolation of supply (consumer unit, fuse box, distribution board) under controlled conditions within a college environment. Demonstration shows how to check an approved voltage indicator on a proving unit and carry out the test to prove dead as 230 volt AC single phase supply in the safest manor.
🔔 Subscribe for more free electrical training videos https://youtube.com/c/GSHElectrical?sub_confirmation=1
= 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - Safe isolation of a single phase consumer unit
00:59 - Leaving a lighting circuit on or using a plug in voltage indicator
01:22 - Turning off MCB's
01:55 - Remove double pole switch
02:51 - Locking off the supply
04:56 - Using a proving unit on the voltage indicator
06:01 - Proving the consumer unit is isolated
07:06 - Using a proving unit to check my voltage indicator
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.